Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
DIN rail (top hat rail) mounting optional
No
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Overload release current setting
1280.0 - 3200A
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Number of poles
3
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Motor drive integrated
No
Suitable for DIN rail (top hat rail) mounting
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
1SDA072525R1 | E4.2V 3200 EKIP TOUCH LSI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Rated permanent current Iu
3200A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
DIN rail (top hat rail) mounting optional
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Overload release current setting
1280.0 .. 3200A
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Number of poles
3
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Motor drive integrated
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP30
Motor drive optional