Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA072529R1 | E4.2V 3200 EKIP HI-TOUCH LSIG 3P WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Overload release current setting
1280.0 .. 3200A
Number of poles
3
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Rated permanent current Iu
3200A
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
With integrated under voltage release
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Type of electrical connection of main circuit
Connection at separate chassis part
Type of control element
Push button
Integrated earth fault protection
Motor drive optional
Device construction
Built-in device slide-in technique (withdrawable)