Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Number of poles
3
Overload release current setting
1600.0 - 4000A
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive optional
Yes
Motor drive integrated
No
With under voltage release
No
With switched-off indicator
Yes
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
From same serie
1SDA072546R1 | E4.2N 4000 EKIP TOUCH LSIG 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of poles
3
Overload release current setting
1600.0 .. 4000A
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive optional
Motor drive integrated
With under voltage release
With switched-off indicator
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Degree of protection (IP)
IP30
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
From same serie