Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Overload release current setting1600.0 - 4000A
Number of auxiliary contacts as change-over contact4
Degree of protection (IP)IP30
Adjustment range short-term delayed short-circuit release2400.0 - 40000A
Adjustment range undelayed short-circuit release6000.0 - 60000A
Rated voltage690 - 690V
With switched-off indicatorYes
With under voltage releaseNo
Rated permanent current Iu4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Device constructionBuilt-in device slide-in technique (withdrawable)
Number of poles3
Complete device with protection unitYes
Type of control elementPush button
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Motor drive integratedNo
Motor drive optionalYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072562R1 | E4.2H 4000 EKIP DIP LSI 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Overload release current setting

1600.0 .. 4000A

Number of auxiliary contacts as change-over contact

4

Degree of protection (IP)

IP30

Adjustment range short-term delayed short-circuit release

2400.0 .. 40000A

Adjustment range undelayed short-circuit release

6000.0 .. 60000A

Rated voltage

690 .. 690V

With switched-off indicator

With under voltage release

Rated permanent current Iu

4000A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Device construction

Built-in device slide-in technique (withdrawable)

Number of poles

3

Complete device with protection unit

Type of control element

Push button

Position of connection for main current circuit

Connection at separate chassis part

Type of electrical connection of main circuit

Connection at separate chassis part

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Motor drive integrated

Motor drive optional