Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu4000A
Overload release current setting1600.0 - 4000A
Number of poles3
Degree of protection (IP)IP30
Rated voltage690 - 690V
Number of auxiliary contacts as change-over contact4
Adjustment range short-term delayed short-circuit release2400.0 - 40000A
With switched-off indicatorYes
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release6000.0 - 60000A
Type of control elementPush button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Integrated earth fault protectionNo
Position of connection for main current circuitConnection at separate chassis part
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
With under voltage releaseNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072572R1 | E4.2V 4000 EKIP DIP LSI 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

4000A

Overload release current setting

1600.0 .. 4000A

Number of poles

3

Degree of protection (IP)

IP30

Rated voltage

690 .. 690V

Number of auxiliary contacts as change-over contact

4

Adjustment range short-term delayed short-circuit release

2400.0 .. 40000A

With switched-off indicator

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

6000.0 .. 60000A

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Integrated earth fault protection

Position of connection for main current circuit

Connection at separate chassis part

Motor drive integrated

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

DIN rail (top hat rail) mounting optional

Motor drive optional

With under voltage release

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.