Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA072629R1 | E6.2V 5000 EKIP HI-TOUCH LSIG 3P WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
With integrated under voltage release
Motor drive integrated
Degree of protection (IP)
IP30
Overload release current setting
2000.0 .. 5000A
Rated voltage
690 .. 690V
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Motor drive optional
Rated permanent current Iu
5000A
Number of poles
3
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Complete device with protection unit
DIN rail (top hat rail) mounting optional