Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 - 690V
Overload release current setting
2520.0 - 6300A
Rated permanent current Iu
6300A
Suitable for DIN rail (top hat rail) mounting
No
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
3
Complete device with protection unit
Yes
Motor drive optional
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
From same serie
1SDA072641R1 | E6.2H 6300 EKIP DIP LI 3P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 .. 690V
Overload release current setting
2520.0 .. 6300A
Rated permanent current Iu
6300A
Suitable for DIN rail (top hat rail) mounting
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Number of auxiliary contacts as normally open contact
0
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Type of control element
Push button
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
3
Complete device with protection unit
Motor drive optional
Motor drive integrated
Degree of protection (IP)
IP30