Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu6300A
Adjustment range short-term delayed short-circuit release3780.0 - 63000A
Overload release current setting2520.0 - 6300A
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
With switched-off indicatorYes
Number of poles3
Type of control elementPush button
Motor drive optionalYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Integrated earth fault protectionYes
Type of electrical connection of main circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
Rated voltage690 - 690V
Adjustment range undelayed short-circuit release9450.0 - 94500A
Degree of protection (IP)IP30
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive integratedNo
Position of connection for main current circuitConnection at separate chassis part
Complete device with protection unitYes
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072643R1 | E6.2H 6300 EKIP DIP LSIG 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

6300A

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Overload release current setting

2520.0 .. 6300A

Number of auxiliary contacts as change-over contact

4

With integrated under voltage release

With switched-off indicator

Number of poles

3

Type of control element

Push button

Motor drive optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Integrated earth fault protection

Type of electrical connection of main circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

Rated voltage

690 .. 690V

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Degree of protection (IP)

IP30

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive integrated

Position of connection for main current circuit

Connection at separate chassis part

Complete device with protection unit

DIN rail (top hat rail) mounting optional