Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
378.0 - 6300A
Rated permanent current Iu
630A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
252.0 - 630A
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
945.0 - 9450A
With switched-off indicator
Yes
With under voltage release
No
Number of poles
4
Motor drive optional
Yes
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive integrated
No
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
From same serie
1SDA072710R1 | E1.2N 630 EKIP G HI-TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Adjustment range short-term delayed short-circuit release
378.0 .. 6300A
Rated permanent current Iu
630A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
252.0 .. 630A
DIN rail (top hat rail) mounting optional
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
945.0 .. 9450A
With switched-off indicator
With under voltage release
Number of poles
4
Motor drive optional
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive integrated
Degree of protection (IP)
IP30
Complete device with protection unit
From same serie