Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles4
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu800A
Overload release current setting320.0 - 800A
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
Degree of protection (IP)IP30
Rated voltage690 - 690V
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive integratedNo
With switched-off indicatorYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz50kA
Adjustment range undelayed short-circuit release1200.0 - 12000A
Adjustment range short-term delayed short-circuit release480.0 - 8000A
Integrated earth fault protectionYes
Motor drive optionalYes
With under voltage releaseNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072736R1 | E1.2C 800 EKIP TOUCH LSIG 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

4

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

800A

Overload release current setting

320.0 .. 800A

Number of auxiliary contacts as change-over contact

4

Type of control element

Push button

Degree of protection (IP)

IP30

Rated voltage

690 .. 690V

Position of connection for main current circuit

Connection at separate chassis part

Type of electrical connection of main circuit

Connection at separate chassis part

Motor drive integrated

With switched-off indicator

Device construction

Built-in device slide-in technique (withdrawable)

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

50kA

Adjustment range undelayed short-circuit release

1200.0 .. 12000A

Adjustment range short-term delayed short-circuit release

480.0 .. 8000A

Integrated earth fault protection

Motor drive optional

With under voltage release

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.