Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA072767R1 | E1.2B 1000 EKIP G TOUCH LSIG 4P WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
With integrated under voltage release
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
1000A
Overload release current setting
400.0 .. 1000A
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
Type of electrical connection of main circuit
Connection at separate chassis part
With switched-off indicator
Motor drive integrated
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Type of control element
Push button
Complete device with protection unit
Integrated earth fault protection
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Adjustment range undelayed short-circuit release
1500.0 .. 15000A