Technical specifications

Rated permanent current Iu1250A
Number of poles4
With integrated under voltage releaseNo
Overload release current setting500.0 - 1250A
Rated voltage690 - 690V
Number of auxiliary contacts as normally open contact0
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally closed contact0
Type of control elementPush button
Type of electrical connection of main circuitConnection at separate chassis part
Position of connection for main current circuitConnection at separate chassis part
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release750.0 - 12500A
Adjustment range undelayed short-circuit release1875.0 - 18750A
Integrated earth fault protectionYes
Motor drive integratedNo
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz42kA
Complete device with protection unitYes
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072807R1 | E1.2B 1250 EKIP G TOUCH LSIG 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Rated permanent current Iu

1250A

Number of poles

4

With integrated under voltage release

Overload release current setting

500.0 .. 1250A

Rated voltage

690 .. 690V

Number of auxiliary contacts as normally open contact

0

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

Type of electrical connection of main circuit

Connection at separate chassis part

Position of connection for main current circuit

Connection at separate chassis part

With switched-off indicator

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Integrated earth fault protection

Motor drive integrated

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

42kA

Complete device with protection unit

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive optional

DIN rail (top hat rail) mounting optional