Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Adjustment range short-term delayed short-circuit release
750.0 - 12500A
Rated permanent current Iu
1250A
Integrated earth fault protection
Yes
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
1875.0 - 18750A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
500.0 - 1250A
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
With switched-off indicator
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
From same serie
1SDA072810R1 | E1.2B 1250 EKIP G HI-TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
Rated permanent current Iu
1250A
Integrated earth fault protection
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
Overload release current setting
500.0 .. 1250A
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
With switched-off indicator
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit
From same serie