

Details
- •Low-voltage control systems
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA072817R1 | E1.2C 1250 EKIP G TOUCH LSIG 4P WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage control systems
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
Degree of protection (IP)
IP30
With integrated under voltage release
Overload release current setting
500.0 .. 1250A
Rated voltage
690 .. 690V
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
1875.0 .. 18750A
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
750.0 .. 12500A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Motor drive optional
DIN rail (top hat rail) mounting optional
Rated permanent current Iu
1250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Device construction
Built-in device slide-in technique (withdrawable)
Number of poles
4
Integrated earth fault protection
Complete device with protection unit
Type of control element
Push button