Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
4
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Position of connection for main current circuit
Connection at separate chassis part
Overload release current setting
640.0 - 1600A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Yes
Motor drive optional
Yes
Suitable for DIN rail (top hat rail) mounting
No
Complete device with protection unit
Yes
Type of control element
Push button
Motor drive integrated
No
Degree of protection (IP)
IP30
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
From same serie
1SDA072857R1 | E1.2C 1600 EKIP G TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
50kA
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Number of poles
4
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Position of connection for main current circuit
Connection at separate chassis part
Overload release current setting
640.0 .. 1600A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Number of auxiliary contacts as normally open contact
0
With switched-off indicator
Motor drive optional
Suitable for DIN rail (top hat rail) mounting
Complete device with protection unit
Type of control element
Push button
Motor drive integrated
Degree of protection (IP)
IP30
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as change-over contact
4
From same serie
We use cookies to enhance your experience.