Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated permanent current Iu1600A
Number of poles4
Overload release current setting640.0 - 1600A
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
Rated voltage690 - 690V
Degree of protection (IP)IP30
Complete device with protection unitYes
Integrated earth fault protectionYes
Motor drive integratedNo
Motor drive optionalYes
Adjustment range short-term delayed short-circuit release960.0 - 16000A
Type of electrical connection of main circuitConnection at separate chassis part
Adjustment range undelayed short-circuit release2400.0 - 24000A
DIN rail (top hat rail) mounting optionalNo
Position of connection for main current circuitConnection at separate chassis part
Suitable for DIN rail (top hat rail) mountingNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz66kA
Device constructionBuilt-in device slide-in technique (withdrawable)
With switched-off indicatorYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA072863R1 | E1.2N 1600 EKIP DIP LSIG 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Rated permanent current Iu

1600A

Number of poles

4

Overload release current setting

640.0 .. 1600A

Number of auxiliary contacts as change-over contact

4

Type of control element

Push button

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Complete device with protection unit

Integrated earth fault protection

Motor drive integrated

Motor drive optional

Adjustment range short-term delayed short-circuit release

960.0 .. 16000A

Type of electrical connection of main circuit

Connection at separate chassis part

Adjustment range undelayed short-circuit release

2400.0 .. 24000A

DIN rail (top hat rail) mounting optional

Position of connection for main current circuit

Connection at separate chassis part

Suitable for DIN rail (top hat rail) mounting

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

66kA

Device construction

Built-in device slide-in technique (withdrawable)

With switched-off indicator

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.