Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
With integrated under voltage releaseNo
Number of auxiliary contacts as change-over contact4
With switched-off indicatorYes
Adjustment range undelayed short-circuit release1500 - 15000A
Adjustment range short-term delayed short-circuit release- - -A
Overload release current setting400 - 1000A
Degree of protection (IP)IP30
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of control elementPush button
Integrated earth fault protectionNo
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Type of electrical connection of main circuitConnection at separate chassis part
Position of connection for main current circuitConnection at separate chassis part
Rated permanent current Iu1000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA