Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1000A
Rated voltage
690 - 690V
Overload release current setting
400.0 - 1000A
Integrated earth fault protection
No
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
1500.0 - 15000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
No
Adjustment range short-term delayed short-circuit release
600.0 - 10000A
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
Yes
With switched-off indicator
Yes
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
From same serie
1SDA072922R1 | E2.2H 1000 EKIP DIP LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1000A
Rated voltage
690 .. 690V
Overload release current setting
400.0 .. 1000A
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
1500.0 .. 15000A
Type of electrical connection of main circuit
Connection at separate chassis part
DIN rail (top hat rail) mounting optional
Adjustment range short-term delayed short-circuit release
600.0 .. 10000A
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Complete device with protection unit
With switched-off indicator
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional
Number of poles
4
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA