Aleta.hr
Main Product Image

1SDA072945R1 | E2.2S 1250 EKIP TOUCH LSI 4P WMP

Code: 1615621

ManufacturerRAZNO
Catalog number1SDA072945R1
Type
EAN code8015644767952

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

1250A

Overload release current setting

500.0 - 1250A

Device construction

Built-in device slide-in technique (withdrawable)

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

750.0 - 12500A

Number of auxiliary contacts as change-over contact

4

Suitable for DIN rail (top hat rail) mounting

No

Number of poles

4

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Rated voltage

690 - 690V

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

Yes

Complete device with protection unit

Yes

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Motor drive optional

Yes

Motor drive integrated

No

Adjustment range undelayed short-circuit release

1875.0 - 18750A

Integrated earth fault protection

No

DIN rail (top hat rail) mounting optional

No


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA072945R1 | E2.2S 1250 EKIP TOUCH LSI 4P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

1250A

Overload release current setting

500.0 .. 1250A

Device construction

Built-in device slide-in technique (withdrawable)

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Adjustment range short-term delayed short-circuit release

750.0 .. 12500A

Number of auxiliary contacts as change-over contact

4

Suitable for DIN rail (top hat rail) mounting

Number of poles

4

Type of control element

Push button

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Connection at separate chassis part

With switched-off indicator

Complete device with protection unit

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Motor drive optional

Motor drive integrated

Adjustment range undelayed short-circuit release

1875.0 .. 18750A

Integrated earth fault protection

DIN rail (top hat rail) mounting optional

From same serie