Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1600A
Integrated earth fault protection
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
Rated voltage
690 - 690V
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
With under voltage release
No
DIN rail (top hat rail) mounting optional
No
With switched-off indicator
Yes
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Complete device with protection unit
Yes
Overload release current setting
640.0 - 1600A
Number of poles
4
From same serie
1SDA072964R1 | E2.2B 1600 EKIP TOUCH LI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1600A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
42kA
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
Type of electrical connection of main circuit
Connection at separate chassis part
With under voltage release
DIN rail (top hat rail) mounting optional
With switched-off indicator
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Complete device with protection unit
Overload release current setting
640.0 .. 1600A
Number of poles
4
From same serie