Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated voltage
690 - 690V
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
With switched-off indicator
Yes
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive integrated
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Degree of protection (IP)
IP30
Motor drive optional
Yes
1SDA072973R1 | E2.2N 1600 EKIP DIP LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
1600A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Rated voltage
690 .. 690V
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
With switched-off indicator
Number of poles
4
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Motor drive integrated
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Degree of protection (IP)
IP30
Motor drive optional
We use cookies to enhance your experience.