Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1600A
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
640.0 - 1600A
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Integrated earth fault protection
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
No
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
No
With under voltage release
No
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Motor drive optional
Yes
1SDA072976R1 | E2.2N 1600 EKIP TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1600A
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
66kA
Overload release current setting
640.0 .. 1600A
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Integrated earth fault protection
Type of electrical connection of main circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
DIN rail (top hat rail) mounting optional
With under voltage release
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
Motor drive integrated
Degree of protection (IP)
IP30
Motor drive optional