Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1600A
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
No
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
960.0 - 16000A
Integrated earth fault protection
No
DIN rail (top hat rail) mounting optional
No
Rated voltage
690 - 690V
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
With under voltage release
No
Adjustment range undelayed short-circuit release
2400.0 - 24000A
Overload release current setting
640.0 - 1600A
Degree of protection (IP)
IP30
Motor drive optional
Yes
Complete device with protection unit
Yes
Motor drive integrated
No
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Number of poles
4
From same serie
1SDA072992R1 | E2.2H 1600 EKIP DIP LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
1600A
Type of electrical connection of main circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
960.0 .. 16000A
Integrated earth fault protection
DIN rail (top hat rail) mounting optional
Rated voltage
690 .. 690V
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
With under voltage release
Adjustment range undelayed short-circuit release
2400.0 .. 24000A
Overload release current setting
640.0 .. 1600A
Degree of protection (IP)
IP30
Motor drive optional
Complete device with protection unit
Motor drive integrated
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Number of poles
4
From same serie