

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- - -A
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 - 690V
Overload release current setting
800.0 - 2000A
Adjustment range undelayed short-circuit release
3000.0 - 30000A
With switched-off indicator
Yes
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
No
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
No
Degree of protection (IP)
IP30
Motor drive integrated
No
Rated permanent current Iu
2000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
From same serie
1SDA073031R1 | E2.2H 2000 EKIP DIP LI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Adjustment range short-term delayed short-circuit release
- .. -A
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Rated voltage
690 .. 690V
Overload release current setting
800.0 .. 2000A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
With switched-off indicator
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as normally closed contact
0
Suitable for DIN rail (top hat rail) mounting
Degree of protection (IP)
IP30
Motor drive integrated
Rated permanent current Iu
2000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Type of control element
Push button
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
From same serie
We use cookies to enhance your experience.