Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Rated permanent current Iu2000A
Degree of protection (IP)IP30
Overload release current setting800.0 - 2000A
Motor drive integratedNo
Complete device with protection unitYes
Integrated earth fault protectionYes
Type of control elementPush button
Adjustment range short-term delayed short-circuit release1200.0 - 20000A
Motor drive optionalYes
Type of electrical connection of main circuitConnection at separate chassis part
Rated voltage690 - 690V
Device constructionBuilt-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release3000.0 - 30000A
Position of connection for main current circuitConnection at separate chassis part
Number of poles4
DIN rail (top hat rail) mounting optionalNo
With switched-off indicatorYes
With integrated under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073033R1 | E2.2H 2000 EKIP DIP LSIG 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as change-over contact

4

Rated permanent current Iu

2000A

Degree of protection (IP)

IP30

Overload release current setting

800.0 .. 2000A

Motor drive integrated

Complete device with protection unit

Integrated earth fault protection

Type of control element

Push button

Adjustment range short-term delayed short-circuit release

1200.0 .. 20000A

Motor drive optional

Type of electrical connection of main circuit

Connection at separate chassis part

Rated voltage

690 .. 690V

Device construction

Built-in device slide-in technique (withdrawable)

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

3000.0 .. 30000A

Position of connection for main current circuit

Connection at separate chassis part

Number of poles

4

DIN rail (top hat rail) mounting optional

With switched-off indicator

With integrated under voltage release

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.