Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated voltage
690 - 690V
Rated permanent current Iu
2000A
Overload release current setting
800.0 - 2000A
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
No
Integrated earth fault protection
Yes
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of poles
4
With switched-off indicator
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
From same serie
1SDA073040R1 | E2.2H 2000 EKIP G HI-TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated voltage
690 .. 690V
Rated permanent current Iu
2000A
Overload release current setting
800.0 .. 2000A
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Integrated earth fault protection
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Number of poles
4
With switched-off indicator
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Number of auxiliary contacts as normally open contact
0
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0