Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
2500A
Adjustment range short-term delayed short-circuit release
1500.0 - 25000A
Overload release current setting
1000.0 - 2500A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Yes
Adjustment range undelayed short-circuit release
3750.0 - 37500A
Suitable for DIN rail (top hat rail) mounting
No
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
With under voltage release
No
With switched-off indicator
Yes
DIN rail (top hat rail) mounting optional
No
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Type of control element
Push button
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Motor drive integrated
No
Motor drive optional
Yes
1SDA073056R1 | E2.2S 2500 EKIP TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
2500A
Adjustment range short-term delayed short-circuit release
1500.0 .. 25000A
Overload release current setting
1000.0 .. 2500A
Type of electrical connection of main circuit
Connection at separate chassis part
Integrated earth fault protection
Adjustment range undelayed short-circuit release
3750.0 .. 37500A
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Device construction
Built-in device slide-in technique (withdrawable)
With under voltage release
With switched-off indicator
DIN rail (top hat rail) mounting optional
Position of connection for main current circuit
Connection at separate chassis part
Number of poles
4
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Type of control element
Push button
Degree of protection (IP)
IP30
Complete device with protection unit
Motor drive integrated
Motor drive optional