Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
2000A
Overload release current setting
800.0 - 2000A
Suitable for DIN rail (top hat rail) mounting
No
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
3000.0 - 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
Yes
DIN rail (top hat rail) mounting optional
No
Number of poles
4
Motor drive integrated
No
Integrated earth fault protection
No
With switched-off indicator
Yes
Type of control element
Push button
Complete device with protection unit
Yes
Rated voltage
690 - 690V
Degree of protection (IP)
IP30
Adjustment range short-term delayed short-circuit release
1200.0 - 20000A
From same serie
1SDA073082R1 | E4.2V 2000 EKIP DIP LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
2000A
Overload release current setting
800.0 .. 2000A
Suitable for DIN rail (top hat rail) mounting
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
3000.0 .. 30000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally open contact
0
Device construction
Built-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Number of auxiliary contacts as change-over contact
4
Number of auxiliary contacts as normally closed contact
0
Motor drive optional
DIN rail (top hat rail) mounting optional
Number of poles
4
Motor drive integrated
Integrated earth fault protection
With switched-off indicator
Type of control element
Push button
Complete device with protection unit
Rated voltage
690 .. 690V
Degree of protection (IP)
IP30
Adjustment range short-term delayed short-circuit release
1200.0 .. 20000A