Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated permanent current Iu
3200A
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Overload release current setting
1280.0 - 3200A
Suitable for DIN rail (top hat rail) mounting
No
DIN rail (top hat rail) mounting optional
No
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
Yes
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Integrated earth fault protection
Yes
Motor drive optional
Yes
Type of control element
Push button
Motor drive integrated
No
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
1SDA073139R1 | E4.2S 3200 EKIP HI-TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Rated permanent current Iu
3200A
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Overload release current setting
1280.0 .. 3200A
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Number of auxiliary contacts as normally closed contact
0
Complete device with protection unit
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Number of poles
4
Integrated earth fault protection
Motor drive optional
Type of control element
Push button
Motor drive integrated
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Type of electrical connection of main circuit
Connection at separate chassis part
We use cookies to enhance your experience.