- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
3200A
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Rated voltage
690 - 690V
Overload release current setting
1280.0 - 3200A
Number of poles
4
Integrated earth fault protection
No
Motor drive integrated
No
Adjustment range undelayed short-circuit release
4800.0 - 48000A
With switched-off indicator
Yes
Suitable for DIN rail (top hat rail) mounting
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
With under voltage release
No
DIN rail (top hat rail) mounting optional
No
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
Complete device with protection unit
Yes
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
Degree of protection (IP)
IP30
1SDA073142R1 | E4.2H 3200 EKIP DIP LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated permanent current Iu
3200A
Type of electrical connection of main circuit
Connection at separate chassis part
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Rated voltage
690 .. 690V
Overload release current setting
1280.0 .. 3200A
Number of poles
4
Integrated earth fault protection
Motor drive integrated
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
With switched-off indicator
Suitable for DIN rail (top hat rail) mounting
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
With under voltage release
DIN rail (top hat rail) mounting optional
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
Complete device with protection unit
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Degree of protection (IP)
IP30