Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
3200A
Overload release current setting
1280.0 - 3200A
DIN rail (top hat rail) mounting optional
No
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Adjustment range short-term delayed short-circuit release
1920.0 - 32000A
Adjustment range undelayed short-circuit release
4800.0 - 48000A
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
With switched-off indicator
Yes
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive optional
Yes
Degree of protection (IP)
IP30
Complete device with protection unit
Yes
Motor drive integrated
No
From same serie
1SDA073143R1 | E4.2H 3200 EKIP DIP LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
3200A
Overload release current setting
1280.0 .. 3200A
DIN rail (top hat rail) mounting optional
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Type of electrical connection of main circuit
Connection at separate chassis part
Type of control element
Push button
Motor drive optional
Degree of protection (IP)
IP30
Complete device with protection unit
Motor drive integrated
From same serie