1SDA073145R1 | E4.2H 3200 EKIP TOUCH LSI 4P WMP
Code: 1615791

1SDA073145R1 | E4.2H 3200 EKIP TOUCH LSI 4P WMP

With integrated under voltage release
Type of electrical connection of main circuit
Connection at separate chassis part
Rated permanent current Iu
3200A
DIN rail (top hat rail) mounting optional
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
100kA
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Rated voltage
690 .. 690V
Overload release current setting
1280.0 .. 3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
Suitable for DIN rail (top hat rail) mounting
Number of auxiliary contacts as change-over contact
4
Position of connection for main current circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
Number of auxiliary contacts as normally open contact
0
Motor drive integrated
Degree of protection (IP)
IP30
Type of control element
Push button
Motor drive optional
With switched-off indicator
Complete device with protection unit