Technical specifications

Position of connection for main current circuitConnection at separate chassis part
Number of poles4
Rated voltage690 - 690V
With integrated under voltage releaseNo
Rated permanent current Iu3200A
Type of electrical connection of main circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Degree of protection (IP)IP30
Number of auxiliary contacts as normally closed contact0
Type of control elementPush button
Overload release current setting1280.0 - 3200A
Adjustment range undelayed short-circuit release4800.0 - 48000A
Adjustment range short-term delayed short-circuit release1920.0 - 32000A
Motor drive optionalYes
With switched-off indicatorYes
Suitable for DIN rail (top hat rail) mountingNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
Complete device with protection unitYes
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073148R1 | E4.2H 3200 EKIP HI-TOUCH LSI 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Position of connection for main current circuit

Connection at separate chassis part

Number of poles

4

Rated voltage

690 .. 690V

With integrated under voltage release

Rated permanent current Iu

3200A

Type of electrical connection of main circuit

Connection at separate chassis part

Number of auxiliary contacts as change-over contact

4

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally closed contact

0

Type of control element

Push button

Overload release current setting

1280.0 .. 3200A

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Adjustment range short-term delayed short-circuit release

1920.0 .. 32000A

Motor drive optional

With switched-off indicator

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

Complete device with protection unit

Integrated earth fault protection

DIN rail (top hat rail) mounting optional