1SDA073151R1 | E4.2V 3200 EKIP DIP LI 4P WMP

Code: 1615797

ManufacturerABB
Catalog number1SDA073151R1
Type
EAN code8015644770013

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting1280.0 - 3200A
Number of auxiliary contacts as change-over contact4
With integrated under voltage releaseNo
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Position of connection for main current circuitConnection at separate chassis part
Type of electrical connection of main circuitConnection at separate chassis part
Degree of protection (IP)IP30
Motor drive integratedNo
With switched-off indicatorYes
Adjustment range undelayed short-circuit release4800.0 - 48000A
Adjustment range short-term delayed short-circuit release- - -A
Suitable for DIN rail (top hat rail) mountingNo
DIN rail (top hat rail) mounting optionalNo
Motor drive optionalYes
Type of control elementPush button
Complete device with protection unitYes
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Rated permanent current Iu3200A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073151R1 | E4.2V 3200 EKIP DIP LI 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage control systems
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Overload release current setting

1280.0 .. 3200A

Number of auxiliary contacts as change-over contact

4

With integrated under voltage release

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Position of connection for main current circuit

Connection at separate chassis part

Type of electrical connection of main circuit

Connection at separate chassis part

Degree of protection (IP)

IP30

Motor drive integrated

With switched-off indicator

Adjustment range undelayed short-circuit release

4800.0 .. 48000A

Adjustment range short-term delayed short-circuit release

- .. -A

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Motor drive optional

Type of control element

Push button

Complete device with protection unit

Integrated earth fault protection

Device construction

Built-in device slide-in technique (withdrawable)

Rated permanent current Iu

3200A

Number of poles

4

Rated voltage

690 .. 690V

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA