Details
- •Low-voltage industrial components
- •Power circuit-breaker for trafo/generator/installation protection
- •1 KOM
- •ABB
Technical specifications
1SDA073158R1 | E4.2V 3200 EKIP HI-TOUCH LSI 4P WMP

Why Register?
- View wholesale prices with discounts
- Real-time stock availability
- Access invoices and dispatch notes
- Order history and frequently ordered items
- Exclusive B2B offers
and much more...
Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally open contact
0
Number of poles
4
Number of auxiliary contacts as normally closed contact
0
Rated permanent current Iu
3200A
Motor drive integrated
Type of electrical connection of main circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
With switched-off indicator
Number of auxiliary contacts as change-over contact
4
Type of control element
Push button
Rated voltage
690 .. 690V
Position of connection for main current circuit
Connection at separate chassis part
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Adjustment range short-term delayed short-circuit release
1920.0 .. 32000A
Overload release current setting
1280.0 .. 3200A
Adjustment range undelayed short-circuit release
4800.0 .. 48000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
With under voltage release
Motor drive optional
Device construction
Built-in device slide-in technique (withdrawable)
DIN rail (top hat rail) mounting optional
Complete device with protection unit