

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Overload release current setting
1600.0 - 4000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Rated permanent current Iu
4000A
DIN rail (top hat rail) mounting optional
No
Rated voltage
690 - 690V
Suitable for DIN rail (top hat rail) mounting
No
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
Yes
With switched-off indicator
Yes
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Degree of protection (IP)
IP30
Motor drive optional
Yes
Motor drive integrated
No
Type of control element
Push button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
From same serie
1SDA073203R1 | E4.2V 4000 EKIP DIP LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Overload release current setting
1600.0 .. 4000A
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as normally closed contact
0
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Rated permanent current Iu
4000A
DIN rail (top hat rail) mounting optional
Rated voltage
690 .. 690V
Suitable for DIN rail (top hat rail) mounting
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Number of auxiliary contacts as change-over contact
4
Integrated earth fault protection
With switched-off indicator
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
Complete device with protection unit
Degree of protection (IP)
IP30
Motor drive optional
Motor drive integrated
Type of control element
Push button
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
From same serie
We use cookies to enhance your experience.