Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Overload release current setting
1600.0 - 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
2400.0 - 40000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
4000A
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
6000.0 - 60000A
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Integrated earth fault protection
Yes
With switched-off indicator
Yes
With under voltage release
No
Number of poles
4
Motor drive integrated
No
Degree of protection (IP)
IP30
1SDA073210R1 | E4.2V 4000 EKIP G HI-TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Overload release current setting
1600.0 .. 4000A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
2400.0 .. 40000A
Device construction
Built-in device slide-in technique (withdrawable)
Type of control element
Push button
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
4000A
Position of connection for main current circuit
Connection at separate chassis part
Adjustment range undelayed short-circuit release
6000.0 .. 60000A
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Integrated earth fault protection
With switched-off indicator
With under voltage release
Number of poles
4
Motor drive integrated
Degree of protection (IP)
IP30
We use cookies to enhance your experience.