Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as change-over contact4
Overload release current setting2000 - 5000A
Number of auxiliary contacts as normally closed contact0
Type of control elementPush button
Adjustment range short-term delayed short-circuit release3000 - 50000A
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalNo
Adjustment range undelayed short-circuit release7500 - 75000A
Motor drive optionalYes
Position of connection for main current circuitConnection at separate chassis part
With under voltage releaseNo
Complete device with protection unitYes
Suitable for DIN rail (top hat rail) mountingNo
Integrated earth fault protectionNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Type of electrical connection of main circuitConnection at separate chassis part
Degree of protection (IP)IP30
With switched-off indicatorYes
Rated permanent current Iu5000A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user