Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Overload release current setting
2000.0 - 5000A
Rated voltage
690 - 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Yes
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Yes
Adjustment range undelayed short-circuit release
7500.0 - 75000A
Integrated earth fault protection
No
Device construction
Built-in device slide-in technique (withdrawable)
With under voltage release
No
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
With switched-off indicator
Yes
Motor drive integrated
No
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
No
Rated permanent current Iu
5000A
DIN rail (top hat rail) mounting optional
No
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
From same serie
1SDA073258R1 | E6.2V 5000 EKIP HI-TOUCH LSI 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Overload release current setting
2000.0 .. 5000A
Rated voltage
690 .. 690V
Type of electrical connection of main circuit
Connection at separate chassis part
Complete device with protection unit
Type of control element
Push button
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Number of auxiliary contacts as change-over contact
4
Motor drive optional
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
Integrated earth fault protection
Device construction
Built-in device slide-in technique (withdrawable)
With under voltage release
Number of poles
4
Position of connection for main current circuit
Connection at separate chassis part
With switched-off indicator
Motor drive integrated
Degree of protection (IP)
IP30
Suitable for DIN rail (top hat rail) mounting
Rated permanent current Iu
5000A
DIN rail (top hat rail) mounting optional
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
From same serie
We use cookies to enhance your experience.