Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact0
Overload release current setting2520.0 - 6300A
Number of auxiliary contacts as normally closed contact0
Number of poles4
Rated voltage690 - 690V
Number of auxiliary contacts as change-over contact4
Rated permanent current Iu6300A
With switched-off indicatorYes
Type of electrical connection of main circuitConnection at separate chassis part
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Adjustment range short-term delayed short-circuit release3780.0 - 63000A
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Position of connection for main current circuitConnection at separate chassis part
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
Integrated earth fault protectionNo
Adjustment range undelayed short-circuit release9450.0 - 94500A
Motor drive integratedNo
Type of control elementPush button
Degree of protection (IP)IP30
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073282R1 | E6.2V 6300 EKIP DIP LSI 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally open contact

0

Overload release current setting

2520.0 .. 6300A

Number of auxiliary contacts as normally closed contact

0

Number of poles

4

Rated voltage

690 .. 690V

Number of auxiliary contacts as change-over contact

4

Rated permanent current Iu

6300A

With switched-off indicator

Type of electrical connection of main circuit

Connection at separate chassis part

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Motor drive optional

DIN rail (top hat rail) mounting optional

Position of connection for main current circuit

Connection at separate chassis part

Device construction

Built-in device slide-in technique (withdrawable)

Complete device with protection unit

Integrated earth fault protection

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Motor drive integrated

Type of control element

Push button

Degree of protection (IP)

IP30

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.