Technical specifications

With integrated under voltage release

No

Rated permanent current Iu

6300A

Overload release current setting

2520.0 - 6300A

Adjustment range short-term delayed short-circuit release

3780.0 - 63000A

Integrated earth fault protection

Yes

Type of electrical connection of main circuit

Connection at separate chassis part

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Adjustment range undelayed short-circuit release

9450.0 - 94500A

Device construction

Built-in device slide-in technique (withdrawable)

Rated voltage

690 - 690V

Suitable for DIN rail (top hat rail) mounting

No

DIN rail (top hat rail) mounting optional

No

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Number of poles

4

Motor drive optional

Yes

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally closed contact

0

With switched-off indicator

Yes

Complete device with protection unit

Yes

Motor drive integrated

No

Number of auxiliary contacts as normally open contact

0


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA073286R1 | E6.2V 6300 EKIP TOUCH LSIG 4P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

With integrated under voltage release

Rated permanent current Iu

6300A

Overload release current setting

2520.0 .. 6300A

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Integrated earth fault protection

Type of electrical connection of main circuit

Connection at separate chassis part

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Device construction

Built-in device slide-in technique (withdrawable)

Rated voltage

690 .. 690V

Suitable for DIN rail (top hat rail) mounting

DIN rail (top hat rail) mounting optional

Number of auxiliary contacts as change-over contact

4

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Number of poles

4

Motor drive optional

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally closed contact

0

With switched-off indicator

Complete device with protection unit

Motor drive integrated

Number of auxiliary contacts as normally open contact

0