Aleta.hr
Main Product Image

1SDA073290R1 | E6.2V 6300 EKIP G HI-TOUCH LSIG 4P WMP

Code: 1615906

ManufacturerRAZNO
Catalog number1SDA073290R1
Type
EAN code8015644771409

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Overload release current setting

2520.0 - 6300A

Type of electrical connection of main circuit

Connection at separate chassis part

DIN rail (top hat rail) mounting optional

No

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Rated permanent current Iu

6300A

Integrated earth fault protection

Yes

Adjustment range short-term delayed short-circuit release

3780.0 - 63000A

Suitable for DIN rail (top hat rail) mounting

No

Device construction

Built-in device slide-in technique (withdrawable)

Adjustment range undelayed short-circuit release

9450.0 - 94500A

Rated voltage

690 - 690V

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

With under voltage release

No

Motor drive integrated

No

Complete device with protection unit

Yes

Motor drive optional

Yes

Number of auxiliary contacts as change-over contact

4

Number of poles

4

With switched-off indicator

Yes

Degree of protection (IP)

IP30


From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.

1SDA073290R1 | E6.2V 6300 EKIP G HI-TOUCH LSIG 4P WMP

Main Product Image

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Overload release current setting

2520.0 .. 6300A

Type of electrical connection of main circuit

Connection at separate chassis part

DIN rail (top hat rail) mounting optional

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

Rated permanent current Iu

6300A

Integrated earth fault protection

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Suitable for DIN rail (top hat rail) mounting

Device construction

Built-in device slide-in technique (withdrawable)

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

Rated voltage

690 .. 690V

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

With under voltage release

Motor drive integrated

Complete device with protection unit

Motor drive optional

Number of auxiliary contacts as change-over contact

4

Number of poles

4

With switched-off indicator

Degree of protection (IP)

IP30

From same serie

*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.