  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Number of poles4
Rated permanent current Iu4000A
Overload release current setting1600.0 - 4000A
Number of auxiliary contacts as change-over contact4
Rated voltage690 - 690V
Suitable for DIN rail (top hat rail) mountingNo
Motor drive integratedNo
DIN rail (top hat rail) mounting optionalNo
Position of connection for main current circuitConnection at separate chassis part
With under voltage releaseNo
Motor drive optionalYes
Adjustment range undelayed short-circuit release6000.0 - 60000A
Type of control elementPush button
Degree of protection (IP)IP30
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz150kA
With switched-off indicatorYes
Adjustment range short-term delayed short-circuit release2400.0 - 40000A
Device constructionBuilt-in device slide-in technique (withdrawable)
Integrated earth fault protectionNo
Type of electrical connection of main circuitConnection at separate chassis part
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073318R1 | E6.2V/F 4000 EKIP HI-TOUCH LSI 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Number of poles

4

Rated permanent current Iu

4000A

Overload release current setting

1600.0 .. 4000A

Number of auxiliary contacts as change-over contact

4

Rated voltage

690 .. 690V

Suitable for DIN rail (top hat rail) mounting

Motor drive integrated

DIN rail (top hat rail) mounting optional

Position of connection for main current circuit

Connection at separate chassis part

With under voltage release

Motor drive optional

Adjustment range undelayed short-circuit release

6000.0 .. 60000A

Type of control element

Push button

Degree of protection (IP)

IP30

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

150kA

With switched-off indicator

Adjustment range short-term delayed short-circuit release

2400.0 .. 40000A

Device construction

Built-in device slide-in technique (withdrawable)

Integrated earth fault protection

Type of electrical connection of main circuit

Connection at separate chassis part

Complete device with protection unit