Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
With switched-off indicator
Yes
Adjustment range short-term delayed short-circuit release
3000.0 - 50000A
Adjustment range undelayed short-circuit release
7500.0 - 75000A
DIN rail (top hat rail) mounting optional
No
Overload release current setting
2000.0 - 5000A
Number of poles
4
Integrated earth fault protection
Yes
Rated permanent current Iu
5000A
Complete device with protection unit
Yes
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
No
With under voltage release
No
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
No
Motor drive optional
Yes
Type of electrical connection of main circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Type of control element
Push button
1SDA073347R1 | E6.2V/F 5000 EKIP G TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as normally open contact
0
Rated voltage
690 .. 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
With switched-off indicator
Adjustment range short-term delayed short-circuit release
3000.0 .. 50000A
Adjustment range undelayed short-circuit release
7500.0 .. 75000A
DIN rail (top hat rail) mounting optional
Overload release current setting
2000.0 .. 5000A
Number of poles
4
Integrated earth fault protection
Rated permanent current Iu
5000A
Complete device with protection unit
Number of auxiliary contacts as change-over contact
4
Suitable for DIN rail (top hat rail) mounting
With under voltage release
Position of connection for main current circuit
Connection at separate chassis part
Device construction
Built-in device slide-in technique (withdrawable)
Motor drive integrated
Motor drive optional
Type of electrical connection of main circuit
Connection at separate chassis part
Degree of protection (IP)
IP30
Type of control element
Push button