  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact4
Rated permanent current Iu6300A
Position of connection for main current circuitConnection at separate chassis part
Number of poles4
Overload release current setting2520.0 - 6300A
Rated voltage690 - 690V
Degree of protection (IP)IP30
Number of auxiliary contacts as normally open contact0
Motor drive integratedNo
Number of auxiliary contacts as normally closed contact0
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
With switched-off indicatorYes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz100kA
With integrated under voltage releaseNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Motor drive optionalYes
Complete device with protection unitYes
Adjustment range short-term delayed short-circuit release3780.0 - 63000A
Integrated earth fault protectionYes
Adjustment range undelayed short-circuit release9450.0 - 94500A
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073369R1 | E6.2H/F 6300 EKIP HI-TOUCH LSIG 4P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as change-over contact

4

Rated permanent current Iu

6300A

Position of connection for main current circuit

Connection at separate chassis part

Number of poles

4

Overload release current setting

2520.0 .. 6300A

Rated voltage

690 .. 690V

Degree of protection (IP)

IP30

Number of auxiliary contacts as normally open contact

0

Motor drive integrated

Number of auxiliary contacts as normally closed contact

0

Type of electrical connection of main circuit

Connection at separate chassis part

Type of control element

Push button

With switched-off indicator

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

100kA

With integrated under voltage release

Device construction

Built-in device slide-in technique (withdrawable)

Motor drive optional

Complete device with protection unit

Adjustment range short-term delayed short-circuit release

3780.0 .. 63000A

Integrated earth fault protection

Adjustment range undelayed short-circuit release

9450.0 .. 94500A

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.