Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
3780.0 - 63000A
DIN rail (top hat rail) mounting optional
No
Suitable for DIN rail (top hat rail) mounting
No
Integrated earth fault protection
Yes
Overload release current setting
2520.0 - 6300A
Rated voltage
690 - 690V
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
9450.0 - 94500A
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
With switched-off indicator
Yes
Motor drive integrated
No
Motor drive optional
Yes
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
Yes
From same serie
1SDA073376R1 | E6.2V/F 6300 EKIP TOUCH LSIG 4P WMP

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
6300A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
150kA
Adjustment range short-term delayed short-circuit release
3780.0 .. 63000A
DIN rail (top hat rail) mounting optional
Suitable for DIN rail (top hat rail) mounting
Integrated earth fault protection
Overload release current setting
2520.0 .. 6300A
Rated voltage
690 .. 690V
Device construction
Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally open contact
0
Type of electrical connection of main circuit
Connection at separate chassis part
Number of auxiliary contacts as change-over contact
4
Adjustment range undelayed short-circuit release
9450.0 .. 94500A
Number of auxiliary contacts as normally closed contact
0
Number of poles
4
With switched-off indicator
Motor drive integrated
Motor drive optional
Degree of protection (IP)
IP30
Position of connection for main current circuit
Connection at separate chassis part
Type of control element
Push button
Complete device with protection unit
From same serie