Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
No
Rated permanent current Iu
250A
Rated voltage
690 - 690V
Adjustment range short-term delayed short-circuit release
150.0 - 2500A
Overload release current setting
100.0 - 250A
Integrated earth fault protection
Yes
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range undelayed short-circuit release
375.0 - 3750A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
No
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Yes
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Yes
Suitable for DIN rail (top hat rail) mounting
No
Motor drive integrated
No
Motor drive optional
Yes
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Degree of protection (IP)
IP30
From same serie
1SDA073633R1 | E2.2S 250 EKIP TOUCH LSIG 3P F HR

Details
- Low-voltage industrial components
- Power circuit-breaker for trafo/generator/installation protection
- 1 KOM
- ABB
Technical specifications
With integrated under voltage release
Rated permanent current Iu
250A
Rated voltage
690 .. 690V
Adjustment range short-term delayed short-circuit release
150.0 .. 2500A
Overload release current setting
100.0 .. 250A
Integrated earth fault protection
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz
85kA
Adjustment range undelayed short-circuit release
375.0 .. 3750A
Type of electrical connection of main circuit
Bolt connection
Device construction
Built-in device fixed built-in technique
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact
0
Number of auxiliary contacts as change-over contact
4
With switched-off indicator
Position of connection for main current circuit
Back side
Type of control element
Push button
Complete device with protection unit
Suitable for DIN rail (top hat rail) mounting
Motor drive integrated
Motor drive optional
Number of auxiliary contacts as normally open contact
0
Number of poles
3
Degree of protection (IP)
IP30
From same serie
We use cookies to enhance your experience.