Aleta.hr

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles3
Adjustment range short-term delayed short-circuit release150.0 - 2500A
Rated permanent current Iu250A
Motor drive integratedNo
Type of electrical connection of main circuitBolt connection
Overload release current setting100.0 - 250A
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
Number of auxiliary contacts as normally open contact0
Number of auxiliary contacts as normally closed contact0
Rated voltage690 - 690V
With switched-off indicatorYes
Degree of protection (IP)IP30
Number of auxiliary contacts as change-over contact4
Type of control elementPush button
Position of connection for main current circuitBack side
Device constructionBuilt-in device fixed built-in technique
Integrated earth fault protectionYes
Motor drive optionalYes
Suitable for DIN rail (top hat rail) mountingNo
With under voltage releaseNo
Adjustment range undelayed short-circuit release375.0 - 3750A
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073634R1 | E2.2S 250 EKIP G TOUCH LSIG 3P F HR

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of poles

3

Adjustment range short-term delayed short-circuit release

150.0 .. 2500A

Rated permanent current Iu

250A

Motor drive integrated

Type of electrical connection of main circuit

Bolt connection

Overload release current setting

100.0 .. 250A

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA

Number of auxiliary contacts as normally open contact

0

Number of auxiliary contacts as normally closed contact

0

Rated voltage

690 .. 690V

With switched-off indicator

Degree of protection (IP)

IP30

Number of auxiliary contacts as change-over contact

4

Type of control element

Push button

Position of connection for main current circuit

Back side

Device construction

Built-in device fixed built-in technique

Integrated earth fault protection

Motor drive optional

Suitable for DIN rail (top hat rail) mounting

With under voltage release

Adjustment range undelayed short-circuit release

375.0 .. 3750A

DIN rail (top hat rail) mounting optional

Complete device with protection unit

VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user.