Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Rated permanent current Iu250A
Number of poles3
Number of auxiliary contacts as change-over contact4
Overload release current setting100.0 - 250A
With switched-off indicatorYes
Degree of protection (IP)IP30
Position of connection for main current circuitConnection at separate chassis part
Type of control elementPush button
Integrated earth fault protectionYes
Rated voltage690 - 690V
Type of electrical connection of main circuitConnection at separate chassis part
Motor drive optionalYes
DIN rail (top hat rail) mounting optionalNo
Suitable for DIN rail (top hat rail) mountingNo
Adjustment range undelayed short-circuit release375.0 - 3750A
Adjustment range short-term delayed short-circuit release150.0 - 2500A
Motor drive integratedNo
Device constructionBuilt-in device slide-in technique (withdrawable)
Complete device with protection unitYes
With under voltage releaseNo
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user

1SDA073656R1 | E2.2S 250 EKIP HI-TOUCH LSIG 3P WMP

Main Product Image

Why Register?

  • View wholesale prices with discounts
  • Real-time stock availability
  • Access invoices and dispatch notes
  • Order history and frequently ordered items
  • Exclusive B2B offers

and much more...

Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact

0

Number of auxiliary contacts as normally open contact

0

Rated permanent current Iu

250A

Number of poles

3

Number of auxiliary contacts as change-over contact

4

Overload release current setting

100.0 .. 250A

With switched-off indicator

Degree of protection (IP)

IP30

Position of connection for main current circuit

Connection at separate chassis part

Type of control element

Push button

Integrated earth fault protection

Rated voltage

690 .. 690V

Type of electrical connection of main circuit

Connection at separate chassis part

Motor drive optional

DIN rail (top hat rail) mounting optional

Suitable for DIN rail (top hat rail) mounting

Adjustment range undelayed short-circuit release

375.0 .. 3750A

Adjustment range short-term delayed short-circuit release

150.0 .. 2500A

Motor drive integrated

Device construction

Built-in device slide-in technique (withdrawable)

Complete device with protection unit

With under voltage release

Rated short-circuit breaking capacity lcu at 400 V, 50 Hz

85kA