Details

  • Low-voltage industrial components
  • Power circuit-breaker for trafo/generator/installation protection
  • 1 KOM
  • ABB

Technical specifications

Number of auxiliary contacts as normally closed contact0
Number of auxiliary contacts as normally open contact0
Type of electrical connection of main circuitConnection at separate chassis part
Type of control elementPush button
Overload release current setting100 - 250A
Motor drive integratedNo
Position of connection for main current circuitConnection at separate chassis part
Number of auxiliary contacts as change-over contact4
Adjustment range undelayed short-circuit release375 - 3750A
Device constructionBuilt-in device slide-in technique (withdrawable)
Adjustment range short-term delayed short-circuit release150 - 2500A
Motor drive optionalYes
With under voltage releaseNo
Degree of protection (IP)IP30
Suitable for DIN rail (top hat rail) mountingNo
With switched-off indicatorYes
Integrated earth fault protectionNo
DIN rail (top hat rail) mounting optionalNo
Complete device with protection unitYes
Rated permanent current Iu250A
Number of poles4
Rated voltage690 - 690V
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz85kA
*VPC is wholesale amount without VAT (tax on added value). For wholesale discounts, please register as business user